| Click on the logos below to visit the site |
|
|
|
|
Fire Amendments
Department of Public Safety
Proposed Permanent Rules Relating to Minnesota Uniform Fire Code
7510.3510 RULES AND STANDARDS ADOPTED BY REFERENCE.
The Uniform Fire Code, as promulgated by the International
Conference of Building Officials, and the Western Fire Chiefs Association and
published by the International Fire Code Institute (Whittier, California, 1997)
is incorporated by reference and made a part of Minnesota Rules pursuant to
statutory authority, subject to the alterations and amendments in this chapter.
The Uniform Fire Code is not subject to frequent change and is available at the
State Law Library, 25 Constitution Avenue, Saint Paul, Minnesota
55155.
UNIFORM FIRE CODE AMENDMENTS
7510.3520 ARTICLE 1 – SEC. 101, CODE TITLE; GENERAL; SEC. 103,
INSPECTION AND ENFORCEMENT; SEC. 105, PERMITS.
Subpart 1. Sec. 101.1. Sec. 101.1 of the Uniform Fire Code
is amended to read:
101.1 Title. This code shall be known as the Minnesota Uniform
Fire Code, may be cited as such, and will be referred to herein as "this code."
Subp. 2. Sec. 101.4 Supplemental Rules and Regulations.
Sec. 101.4 of the Uniform Fire Code is amended to read:
101.4.1 Local government amendments to Article 1. Any
jurisdiction which adopts this code is authorized to make amendments, by
ordinance or regulation, to Article 1 of this code to provide a system for
enforcement and administration within the jurisdiction. These amendments shall
be equal to, in addition to, or more stringent than this code. None of the
existing provisions of Article 1 shall be changed nor shall any amendment be
made which interferes with the intent of the existing provisions nor the state
fire marshal's duties and powers thereunder.
101.4.2 Local government rules. Any jurisdiction which adopts
this code is authorized to adopt, by ordinance or regulation, rules for the
prevention and control of fires and fire hazards as may be necessary from time
to time, to carry out the intent of this code, and which may be more restrictive
than this code when the rules are necessary to protect life or property in the
community. The governing body may adopt this code by ordinance. One certified
copy of the ordinance containing the rules shall be filed with the clerk of the
jurisdiction and shall be in effect immediately thereafter, and additional
copies shall be kept in the office of the fire department for distribution to
the public.
Subp. 3. Sec. 103.1.4. Sec. 103.1.4 of the Uniform Fire
Code is amended to read:
103.1.4. Appeals to state fire marshal. As outlined in
Minnesota Statutes, section 299F.011, subdivisions 5 and 5b, any person may
appeal an order issued to them by the state fire marshal or action taken by the
local governing body on issues regulated by this code. Appeals can be made to
determine the suitability of alternate materials and types of construction, to
provide for reasonable interpretations of the provisions of this code, and to
grant variances from orders issued by representatives of the state fire marshal.
Persons wishing to present matters for appeal shall do so in writing and, in the
case of persons who have received written orders, applications for variances
shall be made prior to the expiration of the orders. Orders shall not be
considered to be expired until any time extensions granted by the state fire
marshal have elapsed. The state fire marshal shall not accept applications for
variances after criminal action for noncompliance has been initiated pursuant to
Minnesota Statutes, section 299F.011, subdivision 6.
Subp. 4. Sec. 103.4.2. Sec. 103.4.2 of the Uniform Fire
Code is amended to read:
103.4.2 Service of order and notices. Any order or notice
authorized or required by this code shall be given or served upon the owner,
operator, occupant or other person responsible for the condition or violation
either by oral notification, personal service, or by delivering the same to and
leaving it with some person of suitable age and discretion upon the premises;
or, if no such person is found on the premises, by affixing a copy thereof in a
conspicuous place on the door to the entrance of said premises and by mailing a
copy thereof to such person by mail to the person's last known address. Orders
or notices given orally shall be confirmed by service in writing as herein
provided.
Subp. 5. Sec. 105.3. Sec. 105.3 of the Uniform Fire Code is
amended to read:
105.3 Application for Permit. All applications for a permit
required by this code shall be made to the chief in such form and detail as
required by the chief. Applications for permits shall be accompanied by such
plans as required by the chief.
Subp. 6. Sec. 105.8. Sec. 105.8 of the Uniform Fire Code is
deleted and replaced with the following:
105.8 Permit Required. When required by the chief, a permit
shall be obtained prior to engaging in any activities, operations, practices or
functions listed in this section.
7510.3530 ARTICLE 2 DEFINITIONS AND ABBREVIATIONS.
Subpart 1. Sec. 202A. Sec. 202A of the Uniform Fire Code is
amended by adding definitions to read:
ADULT DAY CARE CENTER is a facility, licensed by the
Department of Human Services under Minnesota Rules, parts 9555.9600 to
9555.9730, that provides a program of adult day care services to functionally
impaired adults for periods of less than 24 hours per day in a setting other
than a participant's home or the residence of the facility's operator.
AISLE is a path or route leading to an exit from occupied
portions of a room or area formed by boundary elements on one or more sides,
such as walls, seats, desks, tables, counters, storage, or equipment.
AUTHORITY HAVING JURISDICTION is any municipal fire code
official serving a particular jurisdiction or the state fire marshal or any of
their authorized representatives.
AUTOMATIC FIRE DETECTOR is a device designed to detect the
presence of smoke or fire and initiate action and includes heat, smoke, flame,
and firegas detectors.
Subp. 2. Sec. 203B. Sec. 203B of the Uniform Fire Code is
amended by amending the following definition to read:
BUILDING CODE is the Minnesota State Building Code adopted
pursuant to Minnesota Statutes, section 16B.61, subdivision 1.
Subp. 3. Sec. 204C. Sec. 204C of the Uniform Fire Code is
amended by amending and adding definitions to read:
CHIEF is the chief officer of the fire department serving the
jurisdiction or the chief's authorized representatives. For purposes of
enforcing this code, the term chief also includes the state fire marshal and the
state fire marshal's representatives.
CORRIDOR is an interior passageway having a length at least
three times its width, having walls, partitions or other obstructions to exit
travel over 6 feet in height on two opposing sides, and having openings from
rooms or similar spaces.
Subp. 4. Sec. 207F. Sec. 207F of the Uniform Fire Code is
amended by adding a definition to read:
FAMILY DAY CARE HOME is a residence, licensed by the
Department of Human Services under Minnesota Rules, parts 9502.0315 to
9502.0445, in which no more than ten children at any one time receive care,
maintenance and supervision by other than their relatives or legal guardians for
less than 24 hours per day.
Subp. 5. Sec. 208G. Sec. 208G of the Uniform Fire Code is
amended by adding definitions to read:
GROUP DAY CARE HOME is a residence, licensed by the Department
of Human Services under Minnesota Rules, parts 9502.0315 to 9502.0445, in which
at least 11 but not more than 14 children receive care, maintenance and
supervision by other than their relatives or legal guardians for less than 24
hours per day.
GUEST ROOM is a room or rooms used or intended to be used for
sleeping purposes. Every 100 square feet of superficial floor area in a
dormitory shall be considered to be a guest room.
Subp. 6. Sec. 211J. Sec. 211J of the Uniform Fire Code is
amended to read:
JURISDICTION is any municipality, district, or other political
subdivision adopting this code for use in its jurisdictional area.
JURISDICTIONAL AREA is the territory of the municipality,
district, or other political subdivision adopting this code.
Subp. 7. Sec. 214M. Sec. 214M of the Uniform Fire Code is
amended by adding and amending definitions to read:
MECHANICAL CODE is the Minnesota Uniform Mechanical Code as
adopted pursuant to Minnesota Statutes, section 16B.61.
MUNICIPALITY is any statutory or home rule charter city,
county, or town meeting the requirements of Minnesota Statutes, section 368.01,
subdivision 1, the University of Minnesota, or the state for public buildings.
Subp. 8. Sec. 216O. Sec. 216O of the Uniform Fire Code is
amended by amending definitions to read:
Group E Occupancies :
Group E Occupancies shall be:
Division 1. Any building used for educational purposes through
the 12th grade by 50 or more persons for more than 12 hours per week or four
hours in any one day.
Division 2. Any building used for educational purposes through
the 12th grade by less than 50 persons for more than 12 hours per week or four
hours in any one day.
Division 3. Any building used for child care purposes for more
than ten children, or for adult day care centers serving four or more ambulatory
and mobile persons who are capable of taking appropriate action for
selfpreservation under emergency conditions as determined by program licensure
provisions. See part 7510.3540 for the protection requirements for facilities
serving both participants who are capable and not capable of taking appropriate
action for selfpreservation.
Group I Occupancies :
Group I Occupancies shall be:
Division 1.1. Nurseries for the fulltime care of children
under the age of six, each accommodating more than four persons; and, hospitals,
sanitariums, nursing homes and similar buildings, each accommodating more than
four persons.
Division 1.2. Health care centers for ambulatory patients
receiving outpatient medical care which may render the patient incapable of
unassisted selfpreservation, each tenant space accommodating more than five
patients.
Division 2. Detoxification centers; homes for children six
years of age or over, each accommodating more than four persons; Class B3
supervised living facilities; and, adult day care centers serving ambulatory,
nonambulatory, mobile, or nonmobile persons who are not mentally or physically
capable of taking appropriate action for selfpreservation under emergency
conditions as determined by program licensure provisions, each accommodating
more than four persons. See part 7510.3540 for the protection requirements for
facilities serving both participants who are capable and not capable of taking
appropriate action for selfpreservation.
Division 3. Mental hospitals, mental sanitariums, jails,
prisons, reformatories, and buildings where personal liberties of inmates are
similarly restrained.
Group R Occupancies :
Group R Occupancies shall be:
Division 1. Hotels and apartment houses; congregate
residences, each accommodating more than ten persons; and Class A2 supervised
living facilities licensed on or after April 11, 1983, and class B2 supervised
living facilities, defined in Sec. 220S, for the mentally retarded, mentally
ill, chemically dependent, and physically handicapped, each accommodating more
than six persons.
Division 2. Not used.
Division 3. Dwellings and lodging houses; congregate
residences accommodating ten persons or less; family day care; group family day
care; and Class A1, Class A2, and Class B1 supervised living facilities, defined
in Sec. 220S, having more than six but not more than 15 ambulatory or mobile
disabled persons, duly licensed before April 11, 1983, and complying with the
requirements for lodging and rooming houses as set forth in Standard No. 101 in
the National Fire Codes, 1973, issued by the National Fire Protection
Association (Boston, Massachusetts, 1973), are classified as Group R, Division 3
Occupancies. For purposes of this code, the requirements for lodging and rooming
houses set forth in Standard No. 101 (1973) are incorporated by reference, are
not subject to frequent change, and are available at the State Law Library, 25
Constitution Avenue, Saint Paul, Minnesota 55155.
Subp. 9. Sec. 217P. Sec. 217P of the Uniform Fire Code is
amended by amending a definition to read:
POWER TAP is a device which is connected to an electrical
receptacle, has builtin overcurrent protection and allows connection of one or
more electrical plugs to supply electricity to other devices and equipment.
Subp. 10. Sec. 219R. Sec. 219R of the Uniform Fire Code is
amended by amending and adding definitions to read:
REQUIRED BY THE CHIEF means determined by the chief to be
directly related to the safeguarding of life and property from the hazards of
fire and uniform for each class or kind of building, structure or property
covered.
ROOM is a space or area bounded by any
obstructions over 6 feet in height which at any time enclose more than 80
percent of the perimeter of the area. In computing the unobstructed perimeter,
openings less than 3 feet in clear width and less than 6 feet 8 inches high
shall not be considered. Aisles and corridors shall not be construed to form
rooms. See LIQUID STORAGE ROOM and see Sec. 7903.2.3 for construction
requirements for rooms where flammable and combustible liquids are used,
dispensed or mixed in
quantities exceeding exempt amounts.
Subp. 11. Sec 220S. Sec. 220S of the Uniform Fire Code is
amended by adding definitions to read:
STATE FIRE MARSHAL is the Minnesota state fire marshal or the
state fire marshal's authorized representatives.
SUPERVISED LIVING FACILITY is a facility in which supervision,
lodging, meals, and, in accordance with the rules of the Department of Human
Services and the Department of Health, counseling and developmental habilitative
or rehabilitative services are provided to persons who are mentally retarded,
chemically dependent, adult mentally ill, or physically handicapped.
Class A1 supervised living facility is a supervised living
facility for six or fewer ambulatory or mobile disabled persons who are capable
of taking appropriate action for selfpreservation under emergency conditions as
determined by program licensure provisions.
Class A2 supervised living facility is a supervised living
facility for more than six ambulatory or mobile disabled persons who are capable
of taking appropriate action for selfpreservation under emergency conditions as
determined by program licensure provisions.
Class B1 supervised living facility is a supervised living
facility for six or fewer ambulatory or nonambulatory, mobile or nonmobile
persons who are not mentally or physically capable of taking appropriate action
for selfpreservation under emergency conditions as determined by program
licensure provisions.
Class B2 supervised living facility is a supervised living
facility for seven to 16 ambulatory or nonambulatory, mobile or nonmobile
persons who are not mentally or physically capable of taking appropriate action
for selfpreservation under emergency conditions as determined by program
licensure provisions.
Class B3 supervised living facility is a supervised living
facility for 17 or more ambulatory or nonambulatory, mobile or nonmobile persons
who are not mentally or physically capable of taking appropriate action for
selfpreservation under emergency conditions as determined by program licensure
provisions.
7510.3540 ARTICLE 8 ADULT DAY CARE CENTERS AND SUPERVISED LIVING
FACILITIES.
The Uniform Fire Code is amended by adding an Article 8 to read:
ARTICLE 8 ADULT DAY CARE
CENTERS AND SUPERVISED LIVING FACILITIES
8.1 General. Adult day care centers and supervised living
facilities shall meet the requirements of this article.
8.2 Classification of Adult Day Care Centers. Adult day care
centers are classified in accordance with the following and must meet the fire
safety requirements for the designated occupancy classification.
8.2.1 Serving only participants capable of
selfpreservation.
Centers serving only participants who are capable of taking
appropriate action for selfpreservation under emergency conditions shall meet
all applicable requirements for Group E, Division 3 Occupancies.
8.2.2 Serving only participants not capable of
selfpreservation. Centers serving only participants who are not capable of
taking appropriate action for selfpreservation under emergency conditions shall
meet all applicable requirements for Group I, Division 2 Occupancies.
8.2.3 Serving both participants capable and participants not
capable of selfpreservation. Centers serving a population that includes both
participants who are capable and participants who are not capable of taking
appropriate action for selfpreservation under emergency conditions shall meet
the occupancy requirements for Group I, Division 2 or Group E, Division 3
Occupancies. In addition to the requirements for Group E, Division 3
Occupancies, the center shall meet the requirements set forth in this section.
8.2.3.1 Population. Not more than 50 percent of the center's
licensed capacity shall be made up of participants who are not capable of taking
appropriate action for selfpreservation under emergency conditions.
8.2.3.2 Location. The center must be located on a floor level
with all exits directly to grade without any intervening stairs.
8.2.3.3 Fire alarm and detection. The center shall be
protected with a complete automatic fire detection system consisting of
automatic smoke detection in all corridors and at the top of all stairways and
automatic detection in boiler and furnace rooms, kitchens, storage rooms,
janitor closets, laundries, and other hazardous areas. In buildings equipped
with manual fire alarm systems, the manual fire alarm and automatic detection
systems shall be electrically interconnected.
8.2.3.4 Evacuation time. The center shall demonstrate the
ability to evacuate the entire population of the center within three minutes.
8.3 Classification of Supervised Living Facilities. Supervised
living facilities are classified in accordance with Article 2 and must meet the
fire safety requirements for the designated occupancy classification.
8.3.1 Class A1 supervised living facilities. Class A1
supervised living facilities must meet Group R, Division 3 Occupancy
requirements.
8.3.2 Class A2 supervised living facilities. Class A2
supervised living facilities must meet Group R, Division 1 Occupancy
requirements.
8.3.3 Class B1 supervised living facilities. Class B1
supervised living facilities meeting the fireprotection provisions of chapter 21
of the National Fire Protection Association Standard No. 101 (Quincy,
Massachusetts, 1985) for impractical evacuation capabilities shall be classified
as Group R, Division 3 Occupancies. For the purposes of this section and section
8.3.4, Standard No. 101 (1985) chapter 21 is incorporated by reference, is not
subject to frequent change and is available at the State Law Library, 25
Constitution Avenue, Saint Paul, Minnesota 55155.
8.3.4 Class B2 supervised living facilities. Class B2
supervised living facilities meeting the fireprotection provisions of chapter 21
of the National Fire Protection Association Standard No. 101 (Quincy,
Massachusetts, 1985) for impractical evacuation capabilities shall be classified
as Group R, Division 1 Occupancies.
8.3.5 Class B3 supervised living facilities. Class B3
supervised living facilities must meet Group I, Division 2
requirements.
7510.3550 ARTICLE 9 FIRE DEPARTMENT ACCESS AND WATER SUPPLY.
Sec. 904. Article 9 of the Uniform Fire Code is amended by
adding sections to read:
SECTION 904 FIRE LANES
904.1 Marking Fire Lanes. The marking of fire lanes on private
and public property shall be designated and approved by the chief.
904.2 Obstruction of Fire Lanes. Parking of motor vehicles in,
or otherwise obstructing, fire lanes shall be prohibited at all times.
7510.3560 ARTICLE 10 – FIRE PROTECTION SYSTEMS AND
EQUIPMENT
Subpart 1. Sec. 1003.1.2 Sec. 1003.1.2 of the Uniform Fire
Code is amended to read:
1003.1.2 Standards. Fireextinguishing systems shall comply
with the National Fire Protection Association Standard No. 13, Standard for the
Installation of Sprinkler Systems (Quincy, Massachusetts, 1996). National Fire
Protection Standard No. 13 is incorporated by reference, is not subject to
frequent change, and is available at the State Law Library, 25 Constitution
Avenue, Saint Paul, Minnesota 55155.
EXCEPTIONS: 1. Fireextinguishing systems complying with
Uniform Building Code Standard 91.
2. Automatic fireextinguishing systems not covered by the Building
Code shall be approved and installed in accordance with approved standards (see
Article 90).
3. Automatic sprinkler systems may be connected to the domestic
water supply main when approved by the chief, provided that the domestic water
supply is of adequate pressure, capacity and sizing for the combined domestic
and sprinkler requirements. In such case, the sprinkler system connection shall
be made between the public water main or meter and the building shutoff valve,
and there shall not be intervening valves or connections. The fire department
connection required by NFPA Standard No. 13 and Uniform Building Code Standard
9-1 may be omitted when approved by the chief.
4. Automatic sprinkler systems in Group R Occupancies four stories
or less may be in accordance with the Building Code requirements for residential
systems.(See the Building Code and U.B.C. Standard 93.)
5. When, in the opinion of the chief, an adequate alternate water
supply for hose stream requirements is provided or available, the water supply
requirements for the sprinkler system hose stream demands may be
modified.
Subp. 2. Sec. 1003.2.9.1. Sec. 1003.2.9 of the Uniform Fire
Code is amended by adding a section to read:
1003.2.9.1 Area separation walls. For the purposes of Section
1003.2.9, area separation walls shall not define separate buildings.
EXCEPTION: Buildings not exceeding three stories in height and
having area separation walls of a fourhour fire resistance rating in conformance
with the Building Code without openings, doors or
penetrations.
Subp. 3. Sec. 1003.3. Sec. 1003.3 of the Uniform Fire Code
is amended to read:
1003.3 Sprinkler System Security, Monitoring and
Alarms.
1003.3.1 Where required. All valves controlling the water
supply for automatic sprinkler systems and water flow switches on all sprinkler
systems serving 20 or more sprinklers shall be electrically
monitored.
EXCEPTION: For existing sprinkler systems, monitoring is
required when the number of sprinklers is 100 or
more.
Valve monitoring and waterflow alarm and trouble signals shall be
distinctively different and shall be automatically transmitted to an approved
central station, remote station or proprietary station or, when approved by the
chief, shall sound an alarm at a constantly attended location.
EXCEPTION: Underground key or hub valves in roadway boxes
provided by the municipality or public utility need not be
monitored.
1003.3.2 Alarms. An approved audible sprinkler flow alarm
shall be provided on the exterior of the building in an approved location. An
approved audible sprinkler flow alarm to alert the occupants shall be provided
in the interior of the building in a normally occupied location. Actuation of
the alarm shall be as set forth in the Building Code. (see U.B.C. Standard
9-1).
EXCEPTION: An audible alarm inside the building is not
required when the sprinkler system is electrically monitored and alarm signals
are transmitted to an approved central station, remote station or proprietary
station.
1003.3.3 Valve Security. All valves controlling water supplies
for automatic sprinklers shall be locked or secured in the open
position.
EXCEPTION: Valves located in a room or space when access is
limited to essential personnel only.
Subp. 4. Sec. 1003.4. Sec. 1003.4 of the Uniform Fire Code
is amended by adding three items to read:
6. At the top of elevator shafts when the shaft is of
noncombustible construction.
7. In the machine rooms of tractiontype elevators which are
located on top of the elevator shaft and are separated from other areas of the
building, other than the shaft, by not less than a onehour fireresistive
occupancy separation.
8.
On the ceiling of rooms containing swimming pools when the pool
area is used exclusively for swimming purposes and when sprinklers are provided
around the perimeter of the pool area.
Subp. 5. Sec. 1004.1.3. Sec. 1004.1 of the Uniform Fire
Code is amended by adding a section to read:
1004.1.3 Modification to standards. In buildings four or less
stories in height which are protected throughout by an automatic sprinkler
system, a Class I or III standpipe system need only meet the pressure
requirements for the sprinkler system.
Subp. 6. Table No. 1004A Standpipe Required Systems.
Table No. 1004A, with footnotes, of the Uniform Fire Code is deleted and
replaced with the following:
TABLE 1004-A -- STANDPIPE REQUIRED SYSTEMS
1 Class II standpipes need
not be provided in basements having an automatic fire-extinguishing system
throughout.
2The standpipe system may be combined with the automatic sprinkler
system. In buildings four or less stories in height which are protected
throughout by an automatic sprinkler system, a standpipe system need only meet
the pressure requirements for the sprinkler system.
3Portions of otherwise sprinklered buildings which are not
protected by automatic sprinklers shall have Class II standpipes installed as
required for the unsprinklered portions.
4In open structures where Class II standpipes may be damaged by
freezing, the building official may authorize the use of Class I standpipes
which are located as required for Class II standpipes.
5 Class II standpipes need not be provided in assembly areas used
solely for worship.
6 For the purposes of this table, occupied roofs of parking
structures shall be considered an additional story. In parking structures, a
tier is a story.
7 When an automatic sprinkler system is installed, the number of
stories shall be four or more.
Subp. 7. Sec. 1005. Sec. 1005 of the Uniform Fire Code is
deleted.
Subp. 8. Sec. 1007.2.1.1. Sec 1007.2.1.1 of the Uniform
Fire Code is amended to read:
1007.2.1.1 When required. An approved manual, automatic, or
manual and automatic fire alarm system shall be provided in accordance with
Section 1007.2.
EXCEPTION: In areas protected by an approved, supervised
automatic sprinkler system, heat detectors required by Section 1007.2 need not
be provided.
Subp. 9. Sec. 1007.2.2.1. Sec. 1007.2.2.1 of the Uniform
Fire Code is amended to read:
1007.2.2.1 General. Group A, Divisions 1, 2 and 2.1
Occupancies shall be provided with an automatic fire alarm system in accordance
with Section 1007.2.2.
EXCEPTIONS: 1. Assembly areas used solely for worship
purposes.
2. Automatic fire alarm systems are not required when an approved
automatic fire extinguishing system is installed throughout the building.
3. Group A Occupancy portions of Group E Occupancies are allowed
to have alarms as required for the Group E Occupancy.
See also Section 1007.2.12.
Subp. 10. Sec. 1007.2.2.2. Sec. 1007.2.2.2 of the Uniform
Fire Code is amended to read:
1007.2.2.2 Fire detectors. Approved automatic fire detectors
shall be installed in laundry rooms, boiler and furnace rooms, mechanical and
electrical rooms, kitchens, storage rooms and similar areas.
Subp. 11. Sec. 1007.2.2.3. Sec. 1007.2.2.3 of the Uniform
Fire Code is deleted.
Subp. 12. Sec. 1007.2.4.1. Sec. 1007.2.4.1 of the Uniform
Fire Code is amended to read:
1007.2.4.1 General. Group E, Divisions 1 and 3 Occupancies
having an occupant load of 50 or more shall be provided with an approved manual
and automatic fire alarm system.
EXCEPTIONS: 1. In buildings protected throughout by an
approved, supervised fire sprinkler system having a local alarm to notify all
occupants, manual fire alarm boxes are only required in the main office and in a
custodial area.
2.
Where all corridors are protected by an approved automatic fire
alarm system having smoke detection, manual fire alarm pull boxes are only
required near exits serving shops, chemistry and physics laboratories, boiler
rooms, industrial technology and industrial arts rooms, kitchens, custodian's
office, and main office.
1007.2.4.1.1 System initiation. When automatic sprinkler
systems are installed or where automatic fire detectors are provided in
accordance with Section 1007.2.4.2, such systems or detectors shall be connected
to the building's fire alarm system and shall sound the fire alarm signal when
activated.
Subp. 13. Sec. 1007.2.4.2. Sec. 1007.2.4.2 of the Uniform
Fire Code is amended to read:
1007.2.4.2 Fire detectors. Approved automatic fire detectors
shall be installed in laundry rooms, boiler and furnace rooms, mechanical and
electrical rooms, shops, laboratories, kitchens, locker rooms, janitors'
closets, storage rooms, lounges and similar areas.
1007.2.4.2.1 Increased travel distance. Smoke detectors shall
be installed when required by the Building Code for increased travel distance to
exits.
1007.2.4.2.2 Exits through adjoining rooms. Smoke detectors
shall be installed when required by the Building Code to allow the only means of
egress from a room to be through adjoining or intervening rooms.
Subp. 14. Sec. 1007.2.7.1.3. Sec. 1007.2.7.1 of the Uniform
Fire Code is amended by adding a section to read:
1007.2.7.1.3 Fire detectors. Approved automatic fire detectors
shall be installed in laundry and soiled linen rooms, boiler and furnace rooms,
mechanical and electrical rooms, shops, laboratories, kitchens, locker rooms,
janitors' closets, trash collection rooms, storage rooms, lounges, gift shops
and similar areas.
Subp. 15. Sec. 1007.2.7.2.4. Sec. 1007.2.7.2.4 of the
Uniform Fire Code is amended to read:
1007.2.7.2.4 Fire detectors. Approved automatic fire detectors
shall be installed in laundry and soiled linen rooms, boiler and furnace rooms,
mechanical and electrical rooms, shops, laboratories, kitchens, locker rooms,
janitors' closets, trash collection rooms, storage rooms, lounges, gift shops,
commissaries and similar areas. An approved smokedetection system shall be
installed throughout resident housing areas, including sleeping rooms and
contiguous day rooms, group activity spaces and other common spaces normally
accessible to residents.
EXCEPTION: Other approved smokedetection arrangements
providing equivalent protection, such as placing detectors in exhaust ducts from
cells or behind protective grills, are allowed when necessary to prevent damage
or tampering.
Subp. 16. Sec. 1007.2.9.2.3. Section 1007.2.9.2.3 of the
Uniform Fire Code is amended to read:
1007.2.9.2.3 Power source. For buildings constructed prior to
August 1, 1989, detectors can receive their power from a battery supply. For
buildings constructed on or after August 1, 1989, detectors shall be connected
to a centralized power source.
7510.3570 ARTICLE 11 GENERAL SAFETY PRECAUTIONS.
Subpart 1. Sec. 1102. Sections 1102.1, 1102.2, 1102.3 and
1102.5 of the Uniform Fire Code are deleted.
Subp. 2. Sec. 1103.3.3.1. Sec. 1103.3.3.1 of the Uniform
Fire Code is amended by adding Exception 5 to read:
5. Christmas trees shall be used, displayed and stored in
accordance with Sec.
1103.3.3.7.
Subp. 3. Sec. 1103.3.3. Sec. 1103.3.3 of the Uniform Fire
Code is amended by adding sections to read:
1103.3.3.7 Christmas trees. The use, display or storage
of natural or resinbearing Christmas trees or is prohibited.
EXCEPTIONS: 1. The use and display of natural or resinbearing
Christmas trees or decorations inside individual dwelling units of Group R,
Divisions 1 and 3 Occupancies is permitted.
2. Natural or resinbearing trees without open flames or electric
light are allowed in Group E Occupancies, Group A Occupancies used for worship
purposes, Group R1 Occupancies used for hotels and congregate residences, Group
B Occupancies and Group M Occupancies.
1103.3.3.7.1 Use of artificial Christmas trees. The use
or display of flameretardant artificial trees with listed electric light
decorations is allowed in all occupancies as long as they meet the requirements
of Section 1103.3.3.7.2.
1103.3.3.7.2 Location. Christmas trees shall not block access
to required exits or obstruct, impair or block access to any fireprotection
device, appliance or equipment.
Subp. 4. Sec. 1107.3. Sec. 1107. of the Uniform Fire Code
is amended by adding a section to read:
1107.3 Unvented Heaters Prohibited. Unvented fuel-burning room
heaters shall not be installed in Group I Occupancies or in sleeping rooms or
bathrooms of Group R Occupancies.
Subp. 5. Sec. 1111.1. Sec. 1111.1 of the Uniform Fire Code
is amended to read:
1111.1 Fireresistive Construction. Required fireresistive
construction, including occupancy separations, area separation walls, exterior
walls due to location on property, draftstop partitions, separations of special
hazards and hazardous areas, verticalopening protection and smoke barriers,
shall be provided and maintained as specified in the Building Code and this code
and shall be properly repaired, restored or replaced when damaged, altered,
breached, penetrated, removed or improperly installed. When buildings regulated
by the Building Code are remodeled or renovated, all materials used must meet
the fireresistive requirements of the Building Code based on the type of
construction.
Subp. 6. Sec. 1111.2.1. Sec. 1111.2.1 of the Uniform Fire
Code is amended to read:
1111.2.1 Installation and maintenance. Required fire
assemblies shall be provided, installed and maintained as specified in the
Building Code and this code. These assemblies shall bear an approved label or
other identification showing their rating and shall be properly installed,
repaired, restored or replaced when lacking, damaged, altered, breached,
penetrated, removed or improperly installed.
Subp. 7. Sec. 1113. Sec. 1113 of the Uniform Fire Code is
deleted and replaced with the following:
SECTION 1113 GUARDRAILS
Guardrails shall be provided to protect unenclosed floor and roof
openings, open and glazed sides of stairways, landings and ramps, and balconies
or porches which are more than 30 inches above grade or the floor below.
Guardrails shall be installed and maintained in accordance with the Building
Code.
EXCEPTION: Existing guardrails which conformed to the code in
effect at the time they were installed are allowed to
continue.
Subp. 8. Sec. 1114. Article 11 of the Uniform Fire Code is
amended by adding a section to read:
SECTION 1114 ATRIA
Atria in buildings shall conform to the requirements of the
Building Code.
EXCEPTION: Existing atria which conformed to the requirements
of the code in effect at the time they were constructed are allowed to continue.
Subp. 9. Sec. 1115. Article 11 of the Uniform Fire Code is
amended by adding a section to read:
SECTION 1115 MEZZANINES
Mezzanines in buildings shall conform to the requirements of the
Building Code.
7510.3580 ARTICLE 12 MAINTENANCE OF MEANS OF EGRESS AND EMERGENCY
ESCAPES.
Subpart 1. Sec. 1201.3. Sec. 1201 of the Uniform Fire Code
is amended by adding a section to read:
1201.3 Special Exiting Provisions for Younger Students. Rooms
in Group E, Divisions 1 and 2 Occupancies used by preschool, kindergarten, first
or secondgrade pupils, and Group E, Division 3 Occupancies shall be located as
required by the Building Code.
Subp. 2. Sec. 1206. Sec. 1206 of the Uniform Fire Code is
amended to read:
SECTION 1206 EMERGENCY ESCAPES
1206.1 General. Emergency escape or rescue windows, doors or
window wells required by the Building Code for sleeping rooms of Group R
Occupancies shall be maintained free of any obstruction, including bars, grates
or similar devices which would impair egress.
EXCEPTION: Bars, grills, grates or similar devices are
allowed, provided that these devices are equipped with approved release
mechanisms which are openable from the inside without the use of a key or
special knowledge or effort, the release mechanisms are maintained operable, and
the building is equipped with smoke detection installed in conformance with this
code.
1206.2 Escape Windows. In Group R Occupancies, escape windows
shall be provided, installed and maintained in sleeping rooms and rooms used for
family day care, group family day care and foster care in conformance with the
Building Code.
EXCEPTIONS: 1. An escape window is not required if the room
has a door that leads directly to the exterior of the building.
2. Escape windows installed prior to April 11, 1983 and having a
clear opening not less than 20 inches in width, 24 inches in height and 5 square
feet in area with a finished sill height not more than 48 inches above the floor
may be allowed to continue.
3. An escape window is not required if the building is protected
throughout by an approved, automatic sprinkler system.
4. Escape windows need not be installed from rooms of existing
buildings having two separate means of escape, provided that the means of escape
are independent of each other and they pass through only one adjacent
nonlockable room or area.
5. Existing escape windows at singlestory resort buildings
installed prior to October 3, 1975 and having a clear opening not less than 20
inches in width, 20 inches in height and 4.5 square feet in area with a finished
sill height not more than 36 inches above the floor may be allowed to
continue.
Subp. 3. Sec. 1207.3. Sec. 1207.3 of the Uniform Fire Code
is amended to read:
1207.3 Locking Devices. Exit doors shall be openable from the
inside without the use of a key or any special knowledge or effort. Exit doors
shall not be locked, chained, bolted, barred, latched or otherwise rendered
unusable. All locking devices shall be of an approved type.
EXCEPTIONS: 1. In Groups A, Division 3; B; F; M and S
Occupancies and in all churches, keylocking hardware may be used on the main
exit when the main exit consists of a single door or pair of doors if there is a
readily visible durable sign on or adjacent to the door stating "THIS DOOR TO
REMAIN UNLOCKED DURING BUSINESS HOURS." The sign shall be in letters not less
than 1 inch (25.4 mm) high on a contrasting background. When unlocked, the
single door or both leaves of a pair of doors must be free to swing without
operation of a latching device. The use of this exception may be revoked by the
chief or building official for due cause.
2. Exit doors from individual dwelling units; Group R, Division 3
congregate residences; and guest rooms of Group R Occupancies having an occupant
load of 10 or less may be provided with a night latch, dead bolt or security
chain, provided such devices are openable from the inside without the use of a
key or tool and mounted at a height not to exceed 48 inches (1,219 mm) above the
finished floor.
3. Listed egresscontrol devices, installed and maintained in
conformance with the Building Code, are allowed in Group E, Division 1
Occupancies and Group A Occupancies in conjunction with Group E, Division 1
Occupancies.
4. Doorlocking arrangements installed and maintained in
conformance with the Building Code are allowed in Group I Occupancies.
5. Existing doorlocking arrangements in Group I Occupancies which
were installed prior to March 20, 1995, and comply with Appendix IIL may be
allowed to continue.
6. In rooms, other than cells, where occupants are being
restrained for safety or security reasons, special locking arrangements which
comply with the requirements of Section 1207.8 are
permitted.
Manually operated edge or surfacemounted flush bolts and surface
bolts are prohibited. When exit doors are used in pairs and approved automatic
flush bolts are used, the door leaf having the automatic flush bolts shall have
no door knob or surfacemounted hardware. The unlatching of any leaf shall not
require more than one operation.
EXCEPTIONS: 1. Group R, Division 3 Occupancies.
2. When a pair of doors serving a room not normally occupied is
needed for the movement of equipment, manually operated edge or surface bolts
may be used and a door closer need not be provided on the inactive
leaf.
Subp. 4. Sec. 1207.8. Sec. 1207 of the Uniform Fire Code is
amended by adding sections to read:
Sec. 1207.8 Special Locking Arrangements. Special locking
arrangements meeting the requirements of this section are permitted for rooms,
other than cells as defined in the Building Code, Appendix Chapter 3, where the
occupants are being restrained for safety or security reasons. The use of this
section may be revoked by the chief or building official for due
cause.
1207.8.1 Locking hardware. Locking devices shall release upon
any of the following conditions:
1. Activation of the automatic sprinkler system,
2. Activation of any automatic fire detection device,
3. Automatic fire alarm system,
4. Loss of electrical power to the locking device or the fire
alarm system, or
5. Activation of the fire alarm trouble signal.
All locking devices shall be designed to fail in the open
position. Following the release of the locking devices for any of the conditions
specified above, relocking of the devices shall be by manual means only at the
door.
1207.8.2 Fire extinguishing system. When special locking
arrangements are used, the room or area being secured must be protected with
quickresponse sprinklers.
1207.8.3 Fire alarm and detection. When special locking
arrangements are used, the room or area and spaces between the room or area and
an outside exit door shall be protected with automatic smoke detection connected
to the building's fire alarm system. If the walls of the room or area do not
extend to the ceiling, automatic smoke detection can be provided in the adjacent
room or area provided that there are no substantial obstructions to delay
activation of the smoke detection.
1207.8.4 Construction. Rooms or areas containing these special
locking arrangements shall be constructed of noncombustible materials having a
minimum of onehour fireresistive construction. Doors separating the room from
other spaces must have a fireprotection rating of not less than 20 minutes.
Doors need not be selfclosing. The interior finish of the wall and ceiling
surfaces must not exceed a Class III (or Class C) flame spread
rating.
1207.8.5 Testing of devices. Special locking arrangements
shall be tested at least monthly to ensure that they will release under the
conditions set forth in this section. Locking arrangements which are found not
to comply with the requirements of this section shall not be used.
Subp. 5. Sec. 1209. Sec. 1209 of the Uniform Fire Code is
amended to read:
SECTION 1209 EXIT CORRIDORS
1209.1 General. Exit corridors shall be constructed and
maintained in accordance with the Building Code. Partitions, rails, counters and
similar space dividers not over 6 feet (1,829 mm) in height shall not be
construed to form corridors.
EXCEPTIONS: 1. For buildings constructed prior to October 3,
1975, see Appendix I-A, Section 2.3.
2. Corridor doors leading to classrooms and offices in Group E
Occupancies need not be maintained selfclosing or automatic closing if the
building is protected throughout by both an approved automatic sprinkler and an
automatic fire alarm system consisting of automatic smoke detection throughout
the corridor exit system.
1209.2 Clothing and Personal Effects. Corridors of Group E
Occupancies shall not be used for the storage of clothing and similar personal
effects.
EXCEPTIONS: 1. Storage of clothing and personal effects is
permitted in corridors which are protected by an automatic sprinkler system.
2. Storage of clothing and personal effects is permitted in
corridors when kept in metal or noncombustible
lockers.
1209.3 Artwork and Decorations. Corridors of Group E
Occupancies shall not be used for the display of child-prepared artwork,
decorations and teaching materials.
EXCEPTION: Childprepared artwork and teaching materials are
allowed to be attached directly to corridor walls and ceilings in Group E
Occupancies, but shall not exceed 20 percent of the wall or ceiling area. Such
materials shall not obstruct or conceal exits, exit signs or any fireprotection
device, appliance or equipment.
Subp. 6. Sec. 1213.4. Sec. 1213 of the Uniform Fire Code is
amended by adding a section to read:
1213.4 Obstructions. All exits shall be maintained free of
obstructions, including the accumulation of snow and ice, which would restrict
their use.
Subp. 7. Sec. 1214. Article 12 of the Uniform Fire Code is
amended by adding a section to read:
SECTION 1214 PEDESTRIAN WALKWAYS
Pedestrian walkways shall be installed and maintained in
conformance with the Building Code.
Subp. 8. Sec. 1215. Article 12 of the Uniform Fire Code is
amended by adding a section to read:
SECTION 1215 ESCALATORS
Escalators shall not be used as a required exit. Escalator
enclosures shall be installed and maintained in conformance with the Building
Code.
7510.3590 ARTICLE 13 EMERGENCY PROCEDURES.
Subpart 1. Sec. 1302.4 Sec. 1302 of the Uniform Fire Code
is amended by adding a section to read:
1302.4 Reporting Fire Alarm Signals. When required by the
chief, the fire department shall be notified upon activation of the fire alarm
signal.
Subp. 2. Sec. 1303.3.3.3 Sec. 1303.3.3 of the Uniform Fire
Code is amended by adding a section to read:
1303.3.3.3 Evacuation procedures. Upon activation of the fire
alarm system or the discovery of fire, staff members shall ensure that all
occupants have evacuated from the room or area in accordance with the emergency
plans required by section 1303.4. Staff members shall close all doors to the
room when exiting the space.
7510.3600 ARTICLE 26 RESURFACING AND REFINISHING.
Subpart 1. Title. The title of Article 26 of the Uniform
Fire Code is deleted and replaced with the following:
ARTICLE 26 RESURFACING AND
REFINISHING
Subp. 2. Sec. 2601. Sec. 2601 of the Uniform Fire Code is
amended to read:
SECTION 2601 SCOPE
Bowling alleys, roller skating rinks, and other public assembly
occupancies shall conform to all other applicable requirements of this code, as
well as the following provisions.
Subp. 3. Sec. 2602. Sec. 2602 of the Uniform Fire Code is
amended to read:
SECTION 2602 PERMITS
No person shall conduct bowling pin refinishing and bowling alley
or floor resurfacing and refinishing operations involving the use and
application of flammable liquids or materials without a local
permit.
Subp. 4. Sec. 2603. The subtitle of Sec. 2603 of the
Uniform Fire Code is amended to read:
SECTION 2603 RESURFACING AND REFINISHING
Subp. 5. Sec. 2604. The subtitle of Sec. 2604 of the
Uniform Fire Code is amended to read:
SECTION 2604 REFINISHING
7510.3610 ARTICLE 52 MOTOR VEHICLE FUELDISPENSING STATIONS.
Subpart 1. Sec. 5201.3.3. Sec. 5201.3 of the Uniform Fire
Code is amended by adding a section to read:
5201.3.3 State fire marshal plan review. Before any
construction for the storage, handling or use of Class I or II liquids in
aboveground tanks is undertaken at motor vehicle fueldispensing stations, plans
or drawings of the installation shall be submitted, in triplicate, to the state
fire marshal for review. The drawings shall be made to scale and shall show the
name of the person, firm, or corporation proposing the installation; its
location, including property lines, adjacent streets or highways and adjacent
surface waters; location and construction of all buildings; tank location,
contents, size and capacity; type, location and layout of dispensing, pumping,
loading and unloading equipment; type and capacity of vents and pressure relief
provided for each tank; and diking, secondary containment and collision
protection provided.
Subp. 2. Sec. 5201.8. Sec. 5201.8 of the Uniform Fire Code
is amended to read:
5201.8 Signs. Signs prohibiting smoking, prohibiting
dispensing into unapproved containers, prohibiting dispensing by persons under
16 years of age and requiring vehicle engines to be stopped during fueling shall
be conspicuously posted within sight of each dispenser.
Subp. 3. Sec. 5201.12. Sec. 5201 of the Uniform Fire Code
is amended by adding a section to read:
5201.12 Age Requirement. Flammable and combustible liquids
shall be dispensed only by persons 16 years of age or older.
Subp. 4. Sec. 5202.3.1. Sec. 5202.3.1 of the Uniform Fire
Code is amended by adding an exception to read:
EXCEPTION: Except as permitted by Section
5202.4.1.
Subp. 5. Sec. 5202.4.1. Sec. 5202.4.1 of the Uniform Fire
Code is amended to read:
5202.4.1 Aboveground tanks. When approved by the chief, Class
I and II liquids are permitted to be dispensed into the fuel tanks of a motor
vehicle from aboveground tanks when such tanks are installed inside special
enclosures in accordance with Sec. 5202.3.6, from protected aboveground tanks
conforming with Appendix IIF or when such dispensing systems meet the
requirements of this section.
5202.4.1.1 Aboveground tank dispensing systems. When approved
by the chief, the dispensing of Class I and Class II liquids from a fuel
dispensing system supplied by exterior aboveground tanks may be permitted under
the conditions set forth in Sections 5202.4.1.1.1 through 5202.4.1.1.10.
5202.4.1.1.1 Number of tanks. Not more than three aboveground
storage tanks shall be used for dispensing at any single dispensing
site.
5202.4.1.1.2 Capacity of tanks. Tanks storing Class I liquids
shall not exceed 6,000 gallons individual capacity. Tanks storing Class II
liquids shall not exceed 10,000 gallons individual capacity.
5202.4.1.1.3 Fuel delivery method. Fuel delivery from
aboveground tanks shall be from the top of the tank with the dispensing line
equipped with an approved antisyphon system.
5202.4.1.1.4 Dispensing lines. Dispensing lines between the
diked area and the dispenser shall be located underground and shall be
completely enclosed in an approved secondary containment piping system. These
lines shall also be equipped with an approved, normally closed solenoid valve at
each dispenser located below the impact valve.
5202.4.1.1.5 Fill pipe and fill openings. The fill pipe
between the fill opening and the diked area shall be underground. In addition to
the normal valving requirements of the code, there shall be a manually operated,
mechanical shutoff valve on the fill line inside the diked area which is
operated from a location outside the dike.
5202.4.1.1.6 Safety precautions. The tanks and piping shall be
safeguarded against collision, spillage, and overfill. The chief may require
additional safeguards on tanks and piping against collision, spillage and
overfill. Dispensing lines and fill piping shall not penetrate the
dike.
5202.4.1.1.7 Lightning protection. Tanks shall be provided
with lightning protection as specified in National Fire Protection Association
Standard 780, Lightning Protection Code, by the National Fire Protection
Association (Quincy, Massachusetts, 1994). Standard 780 is incorporated by
reference, is not subject to frequent change, and is available at the State Law
Library, 25 Constitution Avenue, Saint Paul, Minnesota 55155.
5202.4.1.1.8 Tank location and distance from dispenser. Tank
location and distance from the tank to the dispenser shall be at least 30 feet.
EXCEPTIONS: 1. For operations not open to the public and for
resort operations serving registered guests only, dispensing of Class I liquids
from one tank having a capacity of 560 gallons or less having the dispenser
located on or adjacent to the tank is permitted.
2. For operations not open to the public, dispensing of Class II
liquids from two tanks having a capacity of 1,000 gallons or less having the
dispenser located on or adjacent to the tank is permitted.
3. Special tank enclosures complying with Sec. 5202.3.6 of this
code having the dispenser located on or adjacent to the tank are permitted.
4. Dispensing devices are permitted to be installed on top of or
adjacent to a listed, twohour fireprotected aboveground tank
system.
5202.4.1.1.9 Location of tank. Tanks shall be located not less
than 50 feet from the nearest side of any public way, property line, building,
or combustible storage located on the same property.
EXCEPTION: Aboveground tanks which have a separation distance
of at least 30 feet between the tank and the dispenser may reduce the distances
between the tank, the public way, property line, building, or combustible
storage to 30 feet.
5202.4.1.1.10 Fireprotection for multiple tanks. Where more
than one tank is used, all aboveground tanks shall be protected by an approved
fireprotection system when required by the chief.
Subp. 6. Sec. 5202.4.8. Sec. 5202.4.8 of the Uniform Fire
Code is deleted.
7510.3620 ARTICLE 61 OILBURNING EQUIPMENT.
Subpart 1. Sec. 6105. Sec. 6105 of the Uniform Fire Code is
amended to read:
SECTION 6105 FUEL OIL
The grade of fuel oil used in a burner shall be that for which the
burner is approved and as stipulated by the manufacturer. The installation and
use of waste oil burners shall conform to the provisions of Minnesota Statutes,
section 299F.015.
Subp. 2. Sec. 6107. Article 61 of the Uniform Fire Code is
amended by adding a section to read:
SECTION 6107 QUANTITIES
The quantity of fuel oil stored inside a building shall not exceed
660 gallons.
EXCEPTION: The quantity of fuel oil stored inside a building
can be increased to 1,320 gallons if the area being used for storage is
separated by a minimum of onehour fireresistive construction from other portions
of the building and is protected with an automatic sprinkler
system.
7510.3630 ARTICLE 77 EXPLOSIVE MATERIALS.
Subpart 1. Sec. 7701.3. Sec. 7701.3 of the Uniform Fire
Code is deleted.
Subp. 2. Sec. 7701.4. Sec. 7701.4 of the Uniform Fire Code
is deleted.
7510.3640 ARTICLE 78 FIREWORKS AND PYROTECHNIC SPECIAL EFFECTS
MATERIAL.
Subpart 1. Sec. 7801.3.1.2 Sec. 7801.3.1.2 is amended to
read:
7801.3.1.2 Displays. Permits are required to conduct a
fireworks display. A fireworks display is only permitted when supervised by a
pyrotechnic operator certified by the state fire marshal. Unless specifically
exempted by the jurisdiction, the sponsor of the proposed fireworks display must
submit a written application for permit at least fifteen (15) days in advance of
the date of the display. The permit application shall include a diagram of the
grounds on which the display is to be held showing the point at which the
fireworks are to be discharged; the number, type and size of the fireworks to be
discharged; the location of all buildings, highways, communication lines, and
other possible overhead obstructions; and the lines behind which the audience
will be restrained. For proximate audience displays, the diagram shall also show
the fallout radius for each pyrotechnic device used during the display. At the
time of permit application, the chief shall be consulted regarding requirements
for standby fire apparatus and personnel.
EXCEPTION: Jurisdictions are authorized to not require permits
for displays involving the use of smoke pots, flash pots and theatrical flash
powder for ceremonial, theatrical and musical productions. Such displays must be
conducted in accordance with this
code.
Subp. 2. Sec. 7802.4.4.2. Sec. 7802.4.4.2 of the Uniform
Fire Code is amended to read:
7802.4.4.2 Construction. Mortars shall be approved for use
with the aerial shells to be fired. Mortars shall be constructed of heavy
cardboard, high density polyethylene (HDPE), paper or metal other than cast
iron.
Subp. 3. Sec. 7802.4.9.8.11. Sec. 7802.4.9.8 of the Uniform
Fire Code is amended by adding a section to read:
7802.4.9.8.11 Paper and plastic mortars. Paper and high
density polyethylene (HDPE) mortars shall not be reloaded during the same
display.
7510.3650 ARTICLE 79 FLAMMABLE
AND COMBUSTIBLE LIQUIDS.
Subpart 1. Sec. 7901.3.3. Sec. 7901.3 of the Uniform Fire
Code is amended by adding a section to read:
7901.3.3 State fire marshal review of plans. Before any
construction or new or additional installation for the storage, handling, or use
of flammable liquids in aboveground tanks is undertaken in bulk plants, chemical
plants, refineries, and processing plants, drawings or blueprints shall be
submitted, in triplicate, to the state fire marshal for review.
The drawings shall show the name of the person, firm, or
corporation proposing the installation,; its location,
including property lines, adjacent streets or highways and adjacent surface
waters; location and construction of all buildings; tank location, contents,
size and capacity; type, location and layout of dispensing, pumping, loading and
unloading equipment; type and capacity of vents and pressure relief provided for
each tank; and diking, secondary containment and collision protection
provided.
Subp. 2. Sec. 7904.5.4.2.1. Sec. 7904.5.4.2.1 of the
Uniform Fire Code is amended to read:
7904.5.4.2.1 General. Class I liquids shall be transferred
from a tank vehicle or tank car only into an approved atmospheric tank or
approved portable tank, except as provided in Sections 7904.5.4.2.2 through
7904.5.4.2.6 Class II and IIIA liquids shall be transferred from a tank vehicle
or tank car only into an approved atmospheric tank, approved container or
approved portable tank, except as provided in Sections 7904.5.4.2.2 through
7904.5.4.2.6.
Subp. 3. Sec.
7904.5.4.2.2. Sec. 7904.5.4.2.2 of the Uniform Fire Code is amended to read:
7904.5.4.2.2 Marine craft and special equipment.
Liquids intended for use as motor fuels are allowed to be transferred from tank
vehicles into the fuel tanks of marine craft and motor vehicles when approved by
the chief, and when:
1. The tank vehicle's specific function is that of supplying fuel
to motor vehicles,
2. The operation is not performed where the public has access or
where there is unusual exposure to life or property,
3. The distance between the tank vehicle and vehicle being
refueled does not exceed 50 feet in length, and
4. All equipment is approved for use with the fuel being
transferred.
7510.3660 ARTICLE 81 HIGHPILED COMBUSTIBLE STORAGE.
Subpart 1. Sec. 8102.1. Sec. 8102.1 of the Uniform Fire
Code is amended to read:
8102.1 General. Fireprotection and lifesafety features for
highpiled storage areas shall be in accordance with Section 8102. Nationally
recognized standards or guidelines, as applicable, are allowed to be used when
approved by the chief.
EXCEPTION: Limited highpiled storage areas in Group M
Occupancies not exceeding 5% of the total square footage of the building or not
exceeding 2,500 square feet in size, whichever is less, need not be separated by
firerated construction and need not comply with the smokeventing and curtain
board requirements of this article when these buildings are protected throughout
by an approved automatic sprinkler system.
Subp. 2. Sec. 8102.7. Sec. 8102.7 of the Uniform Fire Code
is amended to read:
8102.7 Smoke and Heat Removal.
8102.7.1 General. When smoke and heat vents are required by
Table 81A, smoke and heat vents shall be provided in accordance with Section
8102.7.
EXCEPTIONS: 1. When required by the chief, mechanical
smokeremoval systems shall be provided in accordance with U.F.C. Standard
813.
2. Frozen food storage classified as a Class I or Class II
commodity is not required to be provided with smoke and heat vents or mechanical
smoke removal when protected by an automatic sprinkler system.
3. In buildings where the highpiled storage is protected by
EarlySuppression FastResponse (ESFR) sprinklers, the chief is allowed to accept
an engineered mechanical smokeremoval system in accordance with Section
8102.7.5.
Subp. 3. Section 8102.7.5. Sec. 8102.7 of the Uniform Fire
Code is amended by adding a section to read:
8102.7.5 Engineered mechanical smoke-removal systems.
Engineered mechanical smoke removal systems shall be designed in accordance with
Sections 905.5 and 905.6 of the Building Code and Article 81 of this code. The
engineering analysis shall be based on a t2 design fire with a minimum heat
release rate in accordance with Table 8102.7.5. The engineering analysis shall
include the characteristics of the fuel load, commodity classification,
commodity storage arrangements, fan spacing, make-up air requirements and
building parameters. Mechanical fan spacing and make-up air shall be uniformly
distributed throughout the high-piled storage area. The effect of sprinklers may
be assumed to have halted the fire growth at the time of sprinkler
activation.
Table 8102.7.5
7510.3670 ARTICLE 82 LIQUEFIED PETROLEUM GASES.
Article 82 of the Uniform Fire Code is deleted in its entirety and
replaced with the following:
ARTICLE 82 LIQUEFIED PETROLEUM GASES
SECTION 8201 NFPA STANDARD NO. 58 INCORPORATED. The
storage, handling, transportation, and use of liquefied petroleum gas and the
installation of all equipment pertinent to systems for such uses shall be
designed, constructed, installed, operated, and maintained in accordance with
the provisions of the National Fire Protection Association Standard No. 58,
Standard for the Storage and Handling of Liquefied Petroleum Gases (Quincy,
Massachusetts, 1995). Standard No. 58, as amended by Section 8202, is
incorporated by reference, is not subject to frequent change, and is available
at the State Law Library, 25 Constitution Avenue, Saint Paul, Minnesota
55155.
SECTION 8202 AMENDMENTS TO
NFPA STANDARD NO. 58
1. Section 31.3. Section 31.3 of NFPA Standard No. 58 is
amended to read:
3-1.3. LPGas systems shall be installed in accordance with
nationally recognized standards that may apply.
2. Section 32.2.7(e). Section 32.2.7(e) of NFPA Standard
No. 58 is amended to read:
(e) The minimum horizontal separation between aboveground LPGas
containers and aboveground tanks containing liquids having flash points below
200 degrees F. (93.4 degrees C.) shall be 20 ft (6 m). No horizontal separation
shall be required between aboveground LPGas containers and underground tanks
containing flammable or combustible liquids installed in accordance with Article
79 of the Uniform Fire Code.
EXCEPTION: This provision shall not apply when LPGas
containers of 125 gal (0.5 m3) or less water capacity are installed adjacent to
fuel oil supply tanks of 660 gal (2.5 m3) or less
capacity.
3. Section 32.2.7(g). Section 32.2.7(g) of NFPA Standard
No. 58 is amended to read:
(g) The minimum separation between LPGas containers and liquefied
hydrogen containers shall be in accordance with Article 75 of the Uniform Fire
Code.
4. Table 32.3.3. Footnotes 2 and 5 of Table 32.3.3 of NFPA
Standard No. 58 are amended to read:
2. Walls constructed of noncombustible materials having a fire
rating of at least one hour as determined by the Building Code.
5. See Article 79 of the Uniform Fire Code for definitions of
flammable and combustible liquids.
5. Section 35.2. Section 35.2 of NFPA Standard No. 58 is
amended to read:
35.2 Reference Standards. LPGas appliances shall be installed
in accordance with this standard and other nationally recognized standards which
may apply.
6. Section 37.2.1. Section 37.2.1 of NFPA Standard No. 58
is amended to read:
37.2.1 Electrical equipment and wiring shall be of a type
specified by and shall be installed in accordance with the Electrical Code for
ordinary locations except that fixed electrical equipment in classified areas
shall comply with 37.2.2.
7. Section 37.2.2. The first sentence of Section 37.2.2 of
NFPA Standard No. 58 is amended to read:
37.2.2 Fixed electrical equipment and wiring installed within
the classified areas specified in Table 37.2.2 shall comply with Table 37.2.2
and shall be installed in accordance with the Electrical Code.
8. Section 72.3. Section 72.3 of NFPA Standard No. 58 is
amended to read:
72.3 Structure or Building Heating. Heating shall be by steam
or hot water radiation or other heating transfer medium with the heat source
located outside the building or structure (see Section 37, Ignition Source
Control), or by electrical appliances listed for Class I, Group D, Division 2
locations, in accordance with the Electrical Code.
9. Chapter 11. Chapter 11 of NFPA Standard No. 58 is deleted.
Submittal of Plans.
SECTION 8203 INSTALLATION OF CONTAINERS Where an underground
container is permitted, plans of its installation, regardless of capacity, shall
be submitted for review to the state fire marshal before construction.
For any installation utilizing aboveground storage containers of
over 2,000 gallons water capacity, or when aggregate water capacity of all
aboveground containers exceeds 4,000 gallons, plans shall be submitted to the
state fire marshal before construction.
7510.3680 ARTICLE 84 MOTION PICTURE PROJECTION.
Article 84 of the Uniform Fire Code is amended by adding a section
to read:
SECTION 8406 VENTILATION
Ventilation for projection rooms and projection equipment shall be
provided and maintained in conformance with the Building Code.
7510.3690 ARTICLE 85 ELECTRICAL
EQUIPMENT AND WIRING.
Article 85 of the Uniform Fire Code is amended by adding a section
to read:
SECTION 8510 NONAPPROVED APPLIANCES Electrical appliances or
fixtures shall not be used unless they are listed for their intended use.
7510.3700 ARTICLE 90 STANDARDS.
Subpart 1. Sec. 9001.4. Section 9001 of the Uniform Fire
Code is amended by adding a section to read:
9001.4 Standards for Group I, Division 3 Occupancies. The
provisions for protection in newly constructed Group I, Division 3 Occupancies
used as detention and correctional facilities shall be in accordance with the
Building Code Appendix Chapter 3.
Subp. 2. Sec. 9002 U.F.C. Standards. The reference to
Uniform Fire Code Standard No. 821 listed under the heading of Article 82 in
Sec. 9002 is deleted.
7510.3710 AMENDMENTS TO
APPENDICES OF UNIFORM FIRE CODE.
Subpart 1. Adoption. Appendices IA, IC, IIA, IIB, IIC, IIF,
IIL, IVA and VID of the Uniform Fire Code, as amended by this part, shall be
deemed a part of this code and shall be enforced as such.
Subp. 2. Appendix IA, Title. The title of Appendix IA of
the Uniform Fire Code is amended to read:
APPENDIX IA LIFE SAFETY
REQUIREMENTS FOR EXISTING BUILDINGS
Subp. 3. Appendix IA, Sec. 1. Appendix IA, Sec. 1, of the
Uniform Fire Code is amended to read:
SECTION 1 GENERAL
1.1 Purpose. The purpose of Appendix IA is to provide a
reasonable degree of safety to persons occupying existing buildings by providing
for alterations to such existing buildings which do not conform with the minimum
requirements of this code or the Building Code. This appendix is intended to
apply to buildings constructed prior to the adoption of the state fire code on
October 3, 1975.
EXCEPTIONS: 1. Group U Occupancies need not comply with this
appendix article.
2. Group R, Division 3 Occupancies need only comply with Sections
2, 6 and 7 of this appendix article.
1.2 Standards for Existing Group I Occupancies. The provisions
of protection in existing Group I, Divisions 1.1, 1.2 and 2 Occupancies shall be
in accordance with the applicable provisions of the Life Safety Code, ANSI/NFPA
101, referred to as Standard No. 101, issued by the National Fire Protection
Association (Quincy, Massachusetts, 1997). Standard No. 101 is incorporated by
reference, is not subject to frequent change and is available at the State Law
Library, 25 Constitution Avenue, Saint Paul, Minnesota 55155.
The provisions of protection in existing Group I, Division 3
Occupancies used as detention and correctional facilities shall be in accordance
with the applicable provisions of the Life Safety Code, ANSI/NFPA 101, referred
to as Standard No. 101, issued by the National Fire Protection Association
(Quincy, Massachusetts, 1997). Standard No. 101 is not subject to frequent
change and is available at the State Law Library, 25 Constitution Avenue, Saint
Paul, Minnesota 55155.
Construction provisions of Standard No. 101 which are more
restrictive than those found in the Building Code shall not be applicable. For
the purposes of this section, construction provisions shall include those
relating to type of construction, automatic fireextinguishing and standpipe
systems, fire alarm and detection systems, vertical opening protection, escape
windows, exits, smoke barriers, handicapped accessibility and hazardous area
separations.
1.3 Exit Requirements for
Existing Buildings. Exits and emergency escapes shall be provided, installed
and maintained as required in Article 12, except as modified by Section 2 of
this appendix.
Subp. 4. Appendix IA, Sec. 2.1. The first paragraph and the
accompanying Exception in Appendix IA, Sec. 2.1, of the Uniform Fire Code are
amended to read:
SECTION 2 EXITS
2.1 Number of Exits. Every basement and every floor above the
first story used for human occupancy shall have access to at least two separate
exits, one of which may be an exterior fire escape complying with Appendix IA,
Sec. 2.4. Subject to the approval of the chief, an approved ladder device may be
used in lieu of a fire escape when the construction feature or location of the
building on the property makes the installation of a fire escape
impractical.
EXCEPTION: In all occupancies, basements and second stories
with an occupant load of less than ten may have one
exit.
Subp. 5. Appendix IA, Sec. 2.3. Appendix IA, Sec. 2.3, of
the Uniform Fire Code is amended to read:
2.3 Corridors. Corridors serving a Group R, Division 1 or
Group I Occupancy having an occupant load of ten or more and corridors serving
other occupancies having an occupant load of 30 or more shall have walls and
ceilings of not less than onehour fireresistive construction as required by the
Building Code. Existing walls surfaced with wood lath and plaster in good
condition or 1/2inch gypsum wallboard or openings with fixed wired glass set in
steel frames are permitted for corridor walls and ceilings and occupancy
separations when approved. Doors opening into such corridors shall be protected
by 20minute fire assemblies or solid wood doors not less than 13/4 inches thick.
Where the existing frame will not accommodate the 13/4 inches thick door, a 13/8
inches thick solid bonded wood core door or equivalent insulated steel door
shall be permitted. Doors shall be selfclosing or automaticclosing by smoke
detection. Transoms and openings other than doors from corridors to rooms shall
comply with the Building Code (see Sec. 1005.8) or shall be covered with a
minimum of 3/4inch plywood or 1/2inch gypsum wallboard or equivalent material on
the room side.
EXCEPTIONS: 1. Existing corridor walls, ceilings, and opening
protection not in compliance with the above may be continued when such buildings
are protected with an approved automatic sprinkler system throughout. Such
sprinkler system may be supplied from the domestic water system if it is of
adequate volume and pressure.
2. Existing corridor walls, ceilings and opening protection in
Group E, Divisions 1 and 2 Occupancies not in compliance with the above may be
continued when such buildings are protected with an approved automatic fire
alarm system which is monitored by a central, proprietary or remote station
service. The fire alarm system shall include automatic smoke detection
throughout the exit system and approved detection in all rooms and areas other
than classrooms and offices.
Subp. 6. Appendix IA, Sec. 3. Appendix IA, Sec. 3, of the
Uniform Fire Code is amended to read:
SECTION 3 ENCLOSURE OF VERTICAL SHAFTS Interior vertical
shafts, including but not limited to stairways, elevator hoistways, and service
and utility shafts, shall be enclosed by a minimum of onehour fireresistive
construction. All openings into such shafts shall be protected with onehour fire
assemblies which shall be maintained selfclosing or be automatic closing by
smoke detection. All other openings shall be fire protected in an approved
manner.
EXCEPTIONS: 1. In other than Group I Occupancies, an enclosure
will not be required for openings serving only one adjacent floor.
2. Vertical openings need not be protected in Group R, Division 3
Occupancies.
3. Vertical openings need not be protected if the building is
protected by an approved automatic sprinkler
system.
Subp. 7. Appendix IA, Sec. 4. Appendix IA, Sec. 4, of the
Uniform Fire Code is amended to read:
SECTION 4 BASEMENT ACCESS OR SPRINKLER PROTECTION An approved
automatic sprinkler system shall be provided in the following basements when
such areas exceed 2,500 square feet (232.3 m2) in size and do not have 20 square
feet (1.86 m2) of opening entirely above the adjoining ground level in each 50
lineal feet (15,240 mm) or fraction thereof of exterior wall on at least one
side of the building:
1. Group A Occupancies used as commercial drinking and dining
establishments;
2. Group A Occupancies used as bowling alleys;
3. Group E Occupancies used for student occupancy;
4. Group I Occupancies; and
5. Group R, Division 1 Occupancies having dwelling units or guest
rooms.
Openings required by this section shall have a minimum dimension
of 30 inches. If any portion of the basement is located more than 75 feet
(22,860 mm) from required openings, the basement shall be provided with an
approved automatic sprinkler system throughout.
Subp. 8. Appendix IA, Sec. 5. Appendix IA, Sec. 5, of the
Uniform Fire Code is amended to read:
SECTION 5 STANDPIPES Any buildings over four stories in height
shall be provided with an approved Class I or Class III standpipe system. When
required by the chief, any building three or four stories in height shall be
provided with an approved Class I or Class III standpipe system.
Subp. 9. Appendix IA, Sec. 6. Appendix IA, Sec. 6, of the
Uniform Fire Code is amended to read:
SECTION 6 SMOKE DETECTORS Smoke detectors shall be provided,
installed and maintained in dwelling units, congregate residences and hotel or
lodging guest rooms in accordance with Section 1007.2.9.
Subp. 10. Appendix IA, Sec. 7. Appendix IA, Sec. 7, of the
Uniform Fire Code is amended to read:
SECTION 7 SEPARATION OF OCCUPANCIES AND HAZARDOUS AREAS
7.1 Occupancy Separations. Occupancy separation shall be
provided as specified in the Building Code (see U.B.C. Section 302). When
approved by the chief, existing wood lath and plaster in good condition or
1/2inch (12.7 mm) gypsum wallboard may be acceptable where onehour occupancy
separations are required.
EXCEPTIONS: 1. In buildings which are protected throughout by
an approved automatic sprinkler system, onehour occupancy separations need not
be provided.
2. An occupancy separation need not be provided between Group A
and Group R, Division 1 Occupancies if the building is provided with a fire
alarm system having automatic smoke detection throughout the Group A
Occupancy.
3. Firerated opening protection need not be provided between Group
A and Group R, Division 1 Occupancies when such openings are designed to resist
the passage of smoke and the openings are protected by an approved automatic
sprinkler system.
4. An occupancy separation need not be provided where two or more
occupancies occur in the same building or structure and are so intermingled that
separations are impracticable provided that the exit provisions and protection
requirements for the more restrictive occupancy are provided.
5. An occupancy separation need not be provided between a Group R,
Division 3 Occupancy with sleeping accommodations for ten or fewer persons and
Group B or Group M Occupancies which are accessory if interconnected smoke
detectors are provided. At least one smoke detector shall be located in the
Group B or Group M Occupancy and additional detectors may be needed in
accordance with manufacturer's instructions. Smoke detectors in the sleeping
areas shall be located as specified in Section 1007.2.9 and shall be audible in
all sleeping areas (see Article 10).
7.2 Separation of Hazardous Areas. Shops, laboratories,
storage rooms exceeding 100 square feet in size, and rooms containing boilers or
central heating plants in Groups A; B; E; F; H; I; M; R, Division 1; and S
Occupancies shall be separated from the rest of the building by not less than a
onehour occupancy separation. When approved by the chief, existing wood lath and
plaster in good condition or 1/2inch (12.7 mm) gypsum wallboard may be
acceptable where onehour occupancy separations are required.
EXCEPTIONS: 1. In Groups A; B; E; F; I; M; and S Occupancies,
a separation need not be provided where the largest piece of fuel equipment does
not exceed 400,000 Btu per hour input.
2. In Group R, Division 1 Occupancies, a separation need not be
provided for such rooms with equipment serving only one dwelling unit.
3. In Groups A; B; E; F; I; M; R, Division 1; and S Occupancies, a
separation need not be provided if the hazardous area is protected with
automatic sprinklers and the doors to such areas are solid core wood doors or
steel insulated doors. Doors shall be selfclosing or automaticclosing by smoke
detection.
Subp. 11. Appendix IIK. The Uniform Fire Code is amended by
adding an Appendix IIK to read:
APPENDIX IIK FIRES OR
BARBECUES ON BALCONIES OR PATIOS
SECTION 1 OPEN FLAME AND FUEL STORAGE PROHIBITED
1.1 Open Flame Prohibited. In any structure containing three
or more dwelling units, no person shall kindle, maintain, or cause any fire or
open flame on any balcony above ground level, or on any ground floor patio
within 15 feet of the structure.
1.2 Fuel Storage Prohibited. No person shall store or use any
fuel, barbecue, torch, or other similar heating or lighting chemical or device
in the locations designated Sec. 1.1.
EXCEPTION: Listed electric or gasfired barbecue grills that
are permanently mounted and wired or plumbed to the building's gas supply or
electrical system and that maintain a minimum clearance of 18 inches on all
sides, unless listed for lesser clearances, may be installed on balconies and
patios when approved by the chief.
Subp. 12. Appendix IIL. The Uniform Fire Code is amended by
adding an Appendix IIL to read:
APPENDIX IIL SPECIAL LOCKING ARRANGEMENTS FOR GROUP I
OCCUPANCIES
SECTION 1 GENERAL When approved by the chief and where there
is a demonstrated safety or security concern for the patients or residents,
existing doorlocking arrangements conforming to this appendix are permitted in
Group I, Divisions 1.1, 1.2 and 2 Occupancies.
1.1 Arrangement. Each egress path shall have not more than one
such locking arrangement.
1.2 Public Use of Space. Public assembly space is not
permitted within the secured area.
SECTION 2 SUPERVISION
Patients or residents shall be supervised by staff personnel at
all times. Keys or devices which function like keys to unlock the doors shall be
carried by staff at all times.
SECTION 3 FIRE DETECTION
The building must be provided throughout with an approved fire
alarm system having automatic smoke detection installed throughout the exit
corridor system.
SECTION 4 RELEASE OF LOCKING DEVICES
All locking devices shall be designed to fail in the open or
unlocked position. The locking devices shall immediately release upon any one or
more of the following conditions:
1. Activation of the fire alarm system,
2. Activation of any automatic fire detector,
3. Activation of an automatic sprinkler system,
4. Activation of the fire alarm system's trouble signal,
5. Loss of electrical power to the device or the fire alarm
system, or
6. Activation of an unlocking arrangement from an approved
location within the secured area.
SECTION 5 RELOCKING OF DEVICES
Relocking of the locking devices can only be by manual means at
the door which is being secured.
SECTION 6 TESTING OF DEVICES AND SYSTEMS
Special locking arrangements shall be tested at least monthly in
conjunction with the fire alarm system to ensure that they will release under
the conditions as set forth above.
SECTION 7 SYSTEMS NOT IN COMPLIANCE
The use of special locking arrangements and related systems which
are found to not comply with the requirements of this chapter shall be
immediately discontinued until such time that the necessary repairs or
modifications can be made.
REPEALER. Minnesota Rules, parts 7510.3330, subparts 2, 3, 5,
7, 8, and 9; 7510.3360, subparts 2, 4, and 6; 7510.3380; 7510.3390; 7510.3400;
7510.3440, subparts 1, 3, 6, and 7; 7510.3450; 7510.3480, subpart 4; 7510.7100;
7510.7200; 7510.7300; 7510.7400; 7510.8200; 7510.8300; 7510.8400; 7510.8500;
7510.9920; 7510.9930; 7510.9935; 7510.9940; 7510.9945; 7510.9950; 7510.9955;
7510.9960; 7510.9965; 7510.9970; 7510.9975; 7510.9980; and 7510.9985 are
repealed.
|